SPECIFICATION FOR INTERCONNECTING POWER AUTO-TRANSFORMERS TABLE OF CONTENTS Page PART I - GENERAL 2 1.1 SCOPE 2 1.2 QUALITY CONTROL 2 1.3 SUBMITTALS 3 PART 2 - PRODUCT 3 2.1 SERVICE REQUIREMENTS 3 2.2 RATINGS 3 2.3 DESIGN REQUIREMENTS 3 2.4 ACCESSORIES 6 PART 3 - EXECUTION 8 3.1 INSPECTION AND TESTING 8 3.2 SHIPPING AND HANDLING 9 3.3 PERFORMANCE 9 APPENDICES A Deleted B Form of Proposal for Interconnecting Power Auto-Transformers (5 sheets) C Interconnecting Power Auto-Transformers Data Sheets (5 sheets) D Transformer Nameplate No. 31017 of Transformer to be replaced 1 SPECIFICATION FOR INTERCONNECTING POWER AUTO-TRANSFORMERS PART I - GENERAL 1.1 SCOPE 1.1.1 Items Included 1.1.1.1 Design, fabricate, test, furnish and deliver an Interconnecting Power Auto- Transformer, including insulating oil and accessories as completely assembled as possible within shipping and handling limitations in accordance with this specification including all data sheets. 1.1.1.2 ONAN/ONAF 65°C rise, 2 winding Interconnecting Power Auto-Transformers. Transformer configuration YNa0[d11] with high side voltages of 132 kV and 154 kV, and low side voltage of 33 kV. Transformer ONAF MVA ratings are 100/100/50 MVA. %Z is 0.395/9.51. Refer to appendix D for equivalent requested nameplate. 1.2 QUALITY CONTROL 1.2.1 Items and Services 1.2.1.1 Control the quality of items and services to meet the requirements of this specification, the applicable sections of the codes and standards listed in Section 1.2.2, and all other contract documents. 1.2.2 Applicable Codes and Standards 1.2.2.1 Design, manufacture and test the specified equipment in accordance with the applicable sections of the following standards, or alternatively equivalent applicable internationally recognized standards, including standards referenced in them, which are in effect at the time of CONTRACT award. IEC 60076 Distribution, Power & Regulating Transformers ANSI/ASTM Specifications for Mineral Insulating Oil used in D3487 Electrical Apparatus NEMA ICS6 Enclosures for Industrial Controls and Systems 2 1.2.2.2 1.2.2.3 Identify in writing any conflicts between the referenced documents for resolution. In general, when resolving conflicts, the following order of precedence shall apply: Transformer nameplate (Appendix D) Transformer Data Sheets (Appendix C) This Specification Referenced Standards CONTRACTOR shall have a Quality Management System that complies with the applicable requirements of ISO 9002:1994 or equivalent National or International Standard (e.g. - BS 5750 Part 2, EN 29002 or ANSI/ASQC Q9002). Quality management shall include subcontractors and suppliers. 1.3 SUBMITTALS 1.3.1 Complete design drawings are required to be submitted with delivery of transformer. PART 2 - PRODUCT 2.1 SERVICE REQUIREMENTS 2.1.1 The transformer shall be suitable for outdoor installation. 2.1.2 The transformer shall be suitable for use as stated in Appendix C and D. 2.2 RATINGS 2.2.1 The transformer ratings, technical and engineering data shall be as listed in Appendix C and D. 2.3 DESIGN REQUIREMENTS 2.3.1 Tank and Base 2.3.1.1 Furnish tanks with welded construction with continuous welding on tank supports. 2.3.1.2 Furnish each transformer base with seismic rated anchor. 2.3.2 Lifting, Moving and Jacking Facilities 2.3.2.1 Furnish lifting, moving and jacking facilities in accordance with IEC standards. 3 2.3.3 Finish 2.3.3.1 Clean, prime and finish paint the equipment in accordance with CONTRACTOR'S standard procedure for outdoor service. Exterior finish color shall be CONTRACTOR'S standard. 2.3.4 Bushings and Terminations 2.3.4.1 Provide standard bushing and terminal markings unless otherwise specified in Appendix C and D. 2.3.4.2 Furnish bushings to meet the applicable requirements of IEC, extra high creepage. 2.3.4.3 Furnish low and high voltage terminals suitable for terminations as specified in Appendix C and D. 2.3.5 Oil 2.3.5.1 Furnish transformer with oil in accordance with ANSI/ASTM - D3487 Type I unless. 2.3.5.2 If possible, transformer shall be factory filled with insulating liquid and sealed prior to shipment provided the jobsite and transportation facilities can handle the additional weight of the insulating liquid. For transformers which will be field filled, 110% of the required oil volume will be supplied in drums. The transformer shall be certified and labeled as not containing polychlorinated biphenyl (PCB) in accordance with EPA guidelines (less than 1 PPM). 2.3.6 Oil Preservation System 2.3.6.1 Furnish CONTRACTOR'S standard sealed tank, inert gas pressure, or conservator/diaphragm oil preservation system with all accessories for rating and voltage class specified in the Appendix C. 2.3.7 Cooling System 2.3.7.1 Furnish the type of cooling as specified in the Appendix C. 2.3.7.2 Furnish standard control logic for operating fans and pumps. 2.3.8 Tap Changers 2.3.8.1 Furnish transformer with on-load tap changers in accordance with IEC as specified in Appendix C and D. 4 2.3.9 Control Cabinet 2.3.9.1 Furnish a control cabinet for housing all the control and power supply equipment located in either segment one, two, or four as designated by IEC Figure 1, unless otherwise specified in Appendix C. 2.3.9.2 Construct control cabinet that meets the requirements of NEMA Standard ICS6 with blank bottom removable, gasketed plate for conduit entrances. Provide padlocking facilities. 2.3.9.3 Furnish cabinet requiring ventilation with dust filters over each intake and exhaust opening. 2.3.9.4 Furnish NEMA 4 type enclosure designed to prevent accumulation of contaminants along and above closed access door, unless otherwise specified in Appendix C. 2.3.9.5 Furnish thermostatically controlled space heaters rated for use on a 220V ac single phase circuit. Provide adequate lighting and a GFI protected 20 amp receptacle. 2.3.10 Auxiliary Power and Control Supply 2.3.10.1 Furnish equipment including automatic transfer capability from a primary to a backup source suitable for use with CONTRACTOR’S 400V three-phase 50Hz power supply unless otherwise specified in Appendix C. 2.3.10.2 Furnish dc equipment and relays suitable for use with CONTRACTOR’S nominally rated 110V dc system. All devices must be suitable for continuous operation within a range of 90V to 130V dc. 2.3.10.3 Furnish ac equipment nominally rated 220Vac suitable for continuous operation within a range of 90 to 110 percent of rated voltage. Furnish suitable 400-220V control power transformers as required. 2.3.11 Alarms 2.3.11.1 As a minimum, furnish the following: a. Oil low level b. Top oil high temperature c. Winding hot spot high temperature d. Pressure relief device operation e. Sudden or fault pressure relay trip f. Primary to backup power supply transfer 5 2.3.11.2 Furnish 250V dc rated single pole double throw alarm switches. 2.3.11.3 Furnish all switch contact terminals wired to control cabinet terminal blocks. 2.3.12 Wiring 2.3.12.1 Completely wire all control, auxiliary power, and alarm circuits using stranded copper conductors with fire retardant type SIS conductors. 2.3.12.2 Use single-conductor No. 14 AWG minimum, 600V wire for control circuits, single-conductor No. 10 AWG minimum, 600V wire for current transformer (CT) secondary leads, and shielded No. 16 AWG minimum, for low-level signals. Metric equivalent cable sizes may be used. 2.3.12.3 Provide extra flexible wiring over door hinges or other locations where leads may be subjected to flexing. 2.3.12.4 Route wiring so that devices may be removed or serviced without disturbing wiring. Form wire bundles without sharp bends and provide adequate support. 2.3.12.5 Wire all shields and every contact of each device, including spare contacts, to terminal blocks for external connections. 2.3.12.6 Do not connect more than two wires to any single terminal point. Splicing of conductor is not allowed. 2.3.12.7 Terminate all wiring on one side of terminal blocks, leaving the other side entirely free for field cable connections. External wiring shall be arranged for one wire to each terminal point. Use shorting type terminal blocks for CT wiring. 2.3.12.8 Identify internal wiring with CONTRACTOR'S wire number at each end of each wire by a plastic sleeve or similar permanent-type marker. 2.3.12.9 Run wiring from accessory devices in rigid metallic raceway, except for short lengths of cable from fans, pumps, etc. which may be in flexible steel conduit to connect to the rigid conduit system. Provide suitable ground conductor. 2.3.12.10 As an option to the above requirements, CONTRACTOR may propose use of multi-conductor armored cable in lieu of single conductor wire in conduit. 2.4 ACCESSORIES 6 2.4.1 Standard Accessories 2.4.1.1 Furnish all standard accessories in accordance with IEC. Provide all accessory devices that have a monitoring function with contacts for alarming (see also section 2.3.10). As a minimum, the following accessories should be included: a. Neutral ground resistors, when shown on the data sheets, are to have stainless steel grid material. b. Winding (hottest spot) temperature RTD-100 ohm platinum and temperature indicator with alarm contacts. c. Load tap changers, when shown on the data sheets, shall be equipped with automatic and local/remote manual control and a remote tap indication. d. Oil level and top oil temperature indicator. e. Shorting type terminal blocks on current transformer. 2.4.2 Pressure Devices 2.4.2.1 Furnish a sudden pressure or Buchholz protective relay with contacts wired to terminal blocks for alarm and trip functions (see also paragraph 2.3.12.1). 2.4.2.2 Furnish a pressure relief device with contacts wired to terminal blocks for alarming. 2.4.3 Tools 2.4.3.1 Furnish a complete set of special tools necessary for installation and maintenance of the transformer and auxiliary apparatus mounted on it. 7 PART 3 - EXECUTION 3.1 INSPECTION AND TESTING 3.1.1 General: Routine and design tests will be conducted in accordance with ANSI C57.12 or IEC 76.1 3.1.1.1 BUYER will have the option of witnessing tests. CONTRACTOR shall advise BUYER ten (10) working days in advance of tests. Failure to do so may result in re-performing the tests at CONTRACTOR'S expense. 3.1.1.2 Provide certified test reports for all tests performed. 3.1.1.3 Perform transformer tests with the transformer having its own bushings installed. 3.1.1.4 Perform thermal tests (heat run and loss tests) for each transformer in accordance with ANSI C57.12.00-2000 Table 19. 3.1.2 Required Tests 3.1.2.1 Perform routine transformer tests as identified in Section 8 of ANSI C57.12.00 in accordance with ANSI C57.12.90. 3.1.2.2 Perform routine terminal bushing tests in accordance with ANSI C57.19.00 or supply certified routine test reports from identical units. 3.1.2.3 Perform design transformer tests as identified in table 16 of ANSI C57.12.00 in accordance with ANSI C57.12.90 or supply certified design test reports for duplicate or essentially duplicate transformers. 3.1.2.4 Perform the following other transformer tests in accordance with ANSI C57.12.90 as required by Appendix C. a. Perform insulation power factor tests for the full windings. Conduct test between windings and between each winding separately and ground. b. Perform Partial Discharge Test during the induced voltage test of the high-voltage windings at a number of test voltage levels in accordance with ANSI C57.12.90 Sections 10.6 and 10.7. Submit the level of Partial Discharge considered to be damaging and the maximum level of discharge expected at 100 percent induced test voltage. Investigate partial discharge determined to be damaging by test or found to be in excess of the expected maximum level take the necessary corrective action. Retest the transformer for partial discharge following any correction action. c. Perform front-of-wave impulse tests. 8 d. Perform switching impulse tests using a unidirectional wave of negative polarity. 3.1.1.5 Functionally test all alarm contacts, sudden pressure sensors, current transformers, fans and other auxiliary equipment that form part of the transformer unit. 3.2 SHIPPING AND HANDLING 3.2.1 Preparation for Shipment and Handling 3.2.1.1 Prepare the equipment for shipment so as to protect the case, radiators, core and coils, bushings and all other parts and auxiliary devices or accessories from corrosion, dampness, breakage, or vibration injury that might be encountered in transportation and handling. Manner of packaging shall be such as to prevent tampering or pilfering. 3.2.1.2 Deliver transformer as complete as practicable consistent with shipping limitations and protection requirements for the equipment. 3.2.1.3 Ship transformer in dry nitrogen or dry air in accordance with transformer CONTRACTOR’S standard procedure, with adequate positive pressure and dewpoint of minus 200F or lower if transformer is required to be shipped without oil. 3.2.1.4 When oil is to be shipped separately, ship in containers or tanks specially designed and used for this service. 3.2.1.5 Mark the shipping center of gravity on four sides of the tank to aid riggers in handling. 3.2.2 Shipment 3.2.2.1 Coordinate shipping arrangements, as required, to ensure that transformers arrive onsite with the proper field orientation. 3.2.2.2 Ensure that dimensions meet shipping clearance from the factory to the railroad siding specified as the destination and determine any special routing necessary for the shipment. 3.2.2.3 Monitor any rail shipments by calibrated and certified accelerometers. If the transformer being furnished has been subjected to acceleration and/or deceleration greater than that stated in the design data as the maximum allowable during delivery, CONTRACTOR shall inspect, repair and test the equipment as necessary to meet this specification. 3.3 PERFORMANCE 9 3.3.1 3.3.2 State in the proposal the transformer no-load losses at rated voltage and the load losses at the maximum transformer MVA rating as specified in Appendix C. No-load and load losses shall include losses for cooling equipment required for transformer operation. Provide actual losses of transformer in accordance with testing specified in Section 3.1. 10 APPENDIX B FORM OF PROPOSAL FOR INTERCONNECTING POWER AUTO-TRANFORMERS ENGINEERING INFORMATION Bidder __________________ Transformer Tag __________________ Type (shell or core) _________________ 1. INSTALLATION INFORMATION A. Weight 1) Transformer a) Weight of complete transformer b) Shipping weight lb c) Largest shipping section lb lb 2) Oil a) Net weight lb B. Oil gal C. Transformer dimensions complete, length x width x height _____in in in D. Largest shipping section, length x width x height in in in E. State whether the transformer will be shipped with the permanent tank covers (with temporary covers for bushing and collar flanges) or with temporary tank covers. Indicate extent of field assembly required. F. State whether the transformer will be shipped in the upright or horizontal position. 2. TRANSFORMER DATA A. Complete technical details of the oil preservation system B. Efficiency, including cooler losses, at rated voltage at: 1) 100 percent of maximum rated MVA % 2) 75 percent of maximum rated MVA % B-1 3) 50 percent of maximum rated MVA % KW KW KW KW KW KW KW KW KW C. Losses 1) No-load losses at 75°C: a) 100 percent of rated voltage (guarantee value) b) 105 percent of rated voltage c) 110 percent of rated voltage 2) Load losses at rated voltage at 75°C: a) 100 percent of maximum rated MVA (guarantee value) b) 75 percent of maximum rated MVA c) 50 percent of maximum rated MVA d) Total power requirements of auxiliary cooling equipment at maximum rated MVA (guarantee value) 3) Guaranteed total losses at maximum rated MVA. Total losses shall include no-load loss, load loss and the loss of cooling equipment required for full load operation at normal ratio. 4) Cooler losses at no load, if applicable D. Permissible continuous loadings at rated ambient and rated voltage without exceed standard hot spot temperature for the following conditions: 1) With one radiator cooler unit out of service 2) With the largest separately controlled group of radiator cooler units out of service E. Impedance 1) Impedance at maximum rated MVA % 2) Tolerance 3) Variation of Impedance due to Load Tap Changer (LTC) F. Guaranteed switching surge withstand strength HV winding G. Maximum expected partial discharge (corona) level, at 100 percent induced test voltage, RIV H. Level of corona considered to be damaging I. Guaranteed audible sound level MVA MVA KV Microvolt Microvolt Db B-2 H-Winding X-Winding Y-Winding KV A KV A 3. BUSHING DATA {PR IVA TE } A Line Bushing 1) rated voltage 2) rated current 3) Manufacture 4) Type 5) Catalog No. B Neutral Bushing 1) rated voltage 2) rated current 3) Manufacture 4) Type 5) Catalog No. KV A KV A KV A KV A 4. PROTECTIVE DEVICES A . Sudden pressure or Buchholz protective relay 1) Manufacturer 2) Type (include literature in proposal) B. Complete description of combustible gas monitoring C. Surge arresters KV 1) Rating (Voltage Class (MCOV)) 2) Manufacturer 3) Catalog number 5. DRAWINGS A. Preliminary outline drawings furnished with proposal (List drawing numbers.) B. Time required after award of purchase order to furnish preliminary drawings. 1) Outline Weeks 2) Plan of base 3) Schematic or elementary diagram 4) Connection diagram B-3 5) HV and LV bushing flange and terminal details C. Time required after approval of initial drawings to furnish final design drawings Weeks 7. ONSITE STORAGE A. State recommendations for short-term onsite storage (six months or less). B. State recommendations for long-term onsite storage (over six months). 8. EXCEPTIONS A. Does the proposed equipment comply with the specifications? B. If no, the Bidder shall indicate the page in the proposal where the exceptions are found. Company Signature Title Reference Number Date of Bid B-4 APPENDIX C INTERCONNECTING POWER AUTO-TRANFORMER Transformer Tag per appendix D Note: Refer to appendix D for further details. Transformer Function Generator Step-up Startup/Reserve Unit Auxiliary Unit Substation x Auto-Transformer Service Conditions Harmonic Load Currents Other Service Conditions continuous duty, for 50C ambient (55C rise average) Ratings Vector group YNa0[d11) Rated Voltage ratio 154/132/33 kV Base, natural cooling, 75/75/37.5 MVA Maximum, forced cooling, 100/100/50 MVA Frequency 50 Hz Phases per Transformer Tank 3 Maximum available short circuit fault current 1000 MVA at 132 kV for 2 sec. Cooling Method ONAN OFAF X ONAN/ONAF ONAN/OFAF ONAN/ONAF/ONAF ONAN/ONAF/OFAF Other Losses Losses including Cooling Equipment will be evaluated at the following costs: No Load Losses N/A $/KW Load Losses N/A $/KW at maximum rated MVA Terminations C-1 High Side (H) 132kV High Side (X) [154 kV] Low Side (Y) [33kV] Open Bushing Open Bushing Open Bushing X Air Terminal Chamber X Air Terminal Chamber X Air Terminal Chamber Bus Duct Bus Duct Bus Duct Cable Size Cable Size Cable Size Cond./Phase Cond./Phase Cond./Phase Other Other Other Tap Changer X On Load Tap Changer (motorized) equivalent to 3XARSG 3252/521-521/51-22 (20)/0614 Refer to Appendix D Location of Tap Changer Refer to Appendix D Steps Refer to Appendix D X H-Winding X X-Winding Y-Winding Range High Voltage Surge Arresters Required X Not Required Max. Continuous Operating Voltage KV (Line-Ground) Insulated Base Discharge Counter Other Sound Level Audible Sound Level measured in accordance with ANSI/IEEE C57.12.90 at rated voltage with all Cooling Equipment running. Less than n/a Db at 3 feet (1 meter) (A-weighted) Tests All routine, design, and other transformer tests identified in IEEE C57.12.00-2000, Table 19, shall be performed with the exception of those listed below: Insulation Resistance Insulation Power Factor Partial Discharge (Corona) Front of Wave Impulse Switching Impulse X Short Circuit C-2 Auxiliary Power The CONTRACTOR will provide the following: AC power supply Number 2 Rating 400V, 3 ph, 4wire +/- 10% Max. S.C. current 65 kA DC power supply Number 1 Rating will inform Max. S.C. current 40kA Control Cabinet X ANSI/IEEE Standard Location X Enclosure Type, NEMA 4 Other Location Transformer Oil X ANSI/ASTM Standard Other Other Winding Temperature Rise by Resistance Maximum hot spot temperature rise at maximum rated MVA 65 °C 80 °C Impedances at MVA at Reference Temperature of 85°C Refer to Appendix D. Design for Front-of-Wave Impulse Required X Not-Required C-3 H-Winding X-Winding Y-Winding Winding Rated Voltage 154 KV 132 KV 33 KV Winding BIL Min 650 KV Min 650 KV 250 KV Winding Neutral BIL 250 KV Winding Connection Earthed Wye via earthing disconnect switch Delta Neutral Grounding X Solid Resistance None X Solid Resistance None amps secs Solid Resistance X None Rating of Seller Provided Neutral Ground Resister Phase Relationship YNa0[d11] Line Bushing BIL Min 650 KV 650 KV 250 KV Phase to ground voltage 54 mm/kV creep 54 mm/kV creep 54 mm/kV creep Neutral Bushing BIL 250 KV 44 mm/kV creep Line Bushing Location X Cover Side Neutral Bushing Location X Cover Side X Cover Side Cover Side Cover X Side Cover Side Bushing Material Standard Bushing Color Standard Bushing Markings Standard C-4