CLIN DESCRIPTION UNIT QUANTITY UNIT TOTAL PRICE PRICE 0001 Seller shall have the option to supply the switchgear and MCC line ups in accordance with IEC or ANSI standards, depending on their capabilities. A combination of both standards is not acceptable. 
All switchgear shall be manufactured in accordance with project standard 3GS-ES-902 and all applicable IEC or ANSI standards. All motor control centres shall be manufactured in accordance with project standards 3SS-EMC1-902 and all applicable IEC standards or 3SS-ECM1-00001 and all applicable ANSI standards. 
Design ambient temperature shall be 55 degrees C for outdoor units and 40 degrees C for indoor units. 0001A Main Substation 380V Switchboard, 3 phase, 4 wire, 1 EA 2500A, 50kA, 50Hz, IP42 (or equivalent). Incoming, bus tie and feeder circuit breakers and instrumentation shall be as detailed on sheet 1 of the Kirkh Load Schedule. Solid state protection with 50, 51 & 51G functions shall be provided as part of the breaker. 110 VDC batteries and charger shall be included. Batteries to be sized in accordance with the complete switchboard load for a 2 hour duration. 
 0001B Stream Substation 380V Switchboard, 3 phase, 4 wire, 3 EA 2000A, 50kA, 50Hz, IP42 (or equivalent). Incoming, bus tie and feeder circuit breakers and instrumentation shall be as detailed on sheet 2 of the Kirkh Load Schedule. Solid state protection with 50, 51 & 51G functions shall be provided as part of the breaker. 110 VDC batteries and charger shall be included. Batteries to be sized in accordance with the complete switchboard load for a 2 hour duration. 
 0001C Main Lift Station Motor Control Centre. 380V, 3 phase, 1 EA 4 wire, 1250A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 3 of the Kirkh Load Schedule. 
 0001D Sand Removal Motor Control Centre. 380V, 3 phase, 1 EA 4 wire, 630A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 4 of the Kirkh Load Schedule. 
 0001E Detritor MCCs Stream 1 & 2. 380V, 3 phase, 4 wire, 2 EA 400A, 50kA, 50Hz, IP42 (or equivalent). As the MCC is to be located in an outdoor enviroment, an IP55 or NEMA 4 enclosure shall be provided in accordance with appendix B of 3SS-ECM1-902. Motor starters, feeders and instrumentation shall be as detailed on sheet 5 of the Kirkh Load Schedule. 
 CLIN DESCRIPTION UNIT QUANTITY UNIT TOTAL PRICE PRICE 0001F Detritor MCCs Stream (3&4) and (5&6). 380V, 2 EA 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). As the MCC is to be located in an outdoor enviroment, an IP55 or NEMA 4 enclosure shall be provided in accordance with appendix B of 3SS-ECM1-902. Motor starters, feeders and instrumentation shall be as detailed on sheet 5 of the Kirkh Load Schedule. 
 0001G Primary Tank MCCs (Streams 1, 2, 3, 4, 5, 6). 6 EA 380V, 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). As the MCC is to be located in an outdoor enviroment, an IP55 or NEMA 4 enclosure shall be provided in accordance with appendix B of 3SS-ECM1-902. Motor starters, feeders and instrumentation shall be as detailed on sheet 6 of the Kirkh Load Schedule. 
 0001H Aeration stream MCCs (Streams 1, 2, 3, 4, 5 & 6). 380V, 6 EA 3 phase, 4 wire, 630A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 7 of the Kirkh Load Schedule. 
 0001J Return Active Sludge Pump Station MCCs 3 EA (1&2, 3&4, 5&6). 380V, 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 8 of the Kirkh Load Schedule. 
 0001K Final Tank MCCs (Streams 1, 2, 3, 4, 5, 6). 380V, 6 EA 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). As the MCC is to be located in an outdoor enviroment, an IP55 or NEMA 4 enclosure shall be provided in accordance with appendix B of 3SS-ECM1-902. Motor starters, feeders and instrumentation shall be as detailed on sheet 9 of the Kirkh Load Schedule. 
 0001L Oil & Grease Removal MCC. 380V, 3 phase, 4 wire, 1 EA 1250A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 10 of the Kirkh Load Schedule. 
 0001M Wash Water & Fire Water Pumping Station MCC. 1 EA 380V, 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 11 of the Kirkh Load Schedule. 
 CLIN DESCRIPTION UNIT QUANTITY UNIT TOTAL PRICE PRICE 0001N Combined Sludge Pumping Station MCCs. 6 EA (Streams 1, 2, 3, 4, 5 & 6) 380V, 3 phase, 4 wire, 400A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 12 of the Kirkh Load Schedule. 
 0001P Final Effluent Pumping Station MCCs. (#1 & #2) 2 EA 380V, 3 phase, 4 wire, 2000A, 50kA, 50Hz, IP42 (or equivalent). Motor starters, feeders and instrumentation shall be as detailed on sheet 13 of the Kirkh Load Schedule.